Self-ignition of natural gas inside pipes at a regulation station

Otros responsables
Fecha
2008-03-07
Editorial
Elsevier
Revista
Engineering Failure Analysis
Título del libro
Nombre del evento
Fecha del evento
Institución organizadora
ISSN
1350-6307
eISSN
ISBN
Idioma
Inglés
Tipo del evento
Clasificación temática
Palabras clave
Resumen
Expert investigations were developed for a leak followed by fire in a natural gas measurement and regulation station,located in the Southern part of South America. Field inspections, chemical and microstructural tests, mechanical tests and models, and models for deflagration and detonation are presented and discussed. The fire was due to air that got into the pipes, when mounting valves at the pig traps. Venting and bleeding failed to be properly carried out while the line was pressurized, and the filling rate was not regulated properly either. In order to reduce the probability of recurrence of the event, the procedure for the filling and the pressurization of the pipeline was redesigned, safety features added, and personnel trained.
Colecciones
Aprobación
Revisión
Complementado por
Referenciado por
Licencia Creative Commons
Excepto donde se indique lo contrario, la licencia de este ítem se describe como by-nc-sa