Artículo

Inter-Turn Short-Circuit Detection Through Differential Admittance Monitoring in Transformers

Leal Hansen, Gustavo Gabriel Icon; Meira, Matias ; Bossio, Guillermo Rubén Icon; Ruschetti, Cristian Roberto Icon; Verucchi, Carlos

Otros responsables

Fecha

04/2024

Editorial

Institute of Electrical and Electronics Engineers

Revista

Ieee Transactions on Instrumentation and Measurement

Título del libro

Nombre del evento

Fecha del evento

Institución organizadora

ISSN

0018-9456

eISSN

ISBN

Idioma

Inglés

Tipo del evento

Resumen

Early detection of inter-turn short-circuits (ITSCs) in power transformers is essential for ensuring the safe and reliable operation of electrical power systems. Therefore, it is necessary to develop efficient detection strategies. In this article, a strategy for detecting ITSCs of a transformer based on monitoring electrical variables is proposed. An indicator for fault diagnosis obtained from the calculation of differential admittances is proposed. Experimental tests on a 5-kVA transformer validate the proposal. The strategy is sensitive to faults involving 1% of the winding turns with rated current in the fault loop. Besides, it is shown that the fault detection strategy is immune to changes in the load state, undervoltage, load or voltage unbalance, and transformer vector group.

Aprobación

Revisión

Complementado por

Referenciado por

Licencia Creative Commons

Excepto donde se indique lo contrario, la licencia de este ítem se describe como by-nc-sa