Double virtual - impedance loop for inverters with repetitive and droop control in UPS applications
; de Angelo, Cristian Hernan 
Otros responsables
Fecha
03/2022
Editorial
Elsevier Science SA
Revista
Electric Power Systems Research
Título del libro
Nombre del evento
Fecha del evento
Institución organizadora
ISSN
0378-7796
eISSN
1873-2046
ISBN
Idioma
Inglés
Tipo del evento
Clasificación temática
Palabras clave
Resumen
A strategy for the implementation of the output impedance in multi - loop inverters with repetitive control for uninterruptible power supply applications is proposed. The implementation consists of a double virtual-impedance loop with a second-order generalized integrator to independently establish the output impedance in direct current, at the fundamental frequency of the output voltage and its harmonics, with a reduced computational cost. The proposal allows achieving an adequate distribution of the current of a non-linear reference load between inverters connected in parallel with droop control. Design and implementation is experimentally validated considering the requirement of dynamic response, voltage regulation, individual harmonic content and total harmonic distortion of the IEC62040 - 3 and IEC61000 - 2 - 2 standards for two 500 VA inverters prototype connected in parallel and in islanded mode.
Colecciones
Aprobación
Revisión
Complementado por
Referenciado por
Licencia Creative Commons
Excepto donde se indique lo contrario, la licencia de este ítem se describe como by-nc-sa