Resumen
Sweep frequency-response analysis (SFRA) is a powerful technique to detect mechanical damage in transformer windings, such as deformations and displacements, as well as other failures, helping to prevent severe damage. Since SFRA is a sensitive diagnostic technique, there are these days several commercially available measurement instruments to perform the tests, but the failure interpretation is usually based on expert opinion. One of the most advisable ways to face the task of interpretation of SFRA test results is the use of mathematical indices to detect abnormalities along with an interpretation scheme. The failure interpretation methodology of SFRA tests must establish the possible relationships between frequency ranges and specific failures, because different failure types can be detected in different frequency ranges of the SFRA trace. This paper proposes a new methodology for power transformer failure diagnosis using the relationships between the different decomposition levels of the original trace obtained with the use of the discrete wavelet transform and the definition of frequency regions with variable limits, according to the shape of the trace. Moreover, an interpretation map and a vector fitting analysis are also proposed in order to establish a specific failure.
Colecciones
Aprobación
Revisión
Complementado por
Referenciado por
Licencia Creative Commons
Excepto donde se indique lo contrario, la licencia de este ítem se describe como by-nc-sa