Mostrar el registro sencillo del ítem

dc.contributor.author
Flores, Wilfredo C.  
dc.contributor.author
Mombello, Enrique Esteban  
dc.contributor.author
Jardini, José. A.  
dc.contributor.author
Rattá Gutiérrez, Giuseppe Aníbal  
dc.contributor.author
Corvo, Antonio M.  
dc.date.available
2023-03-02T00:47:45Z  
dc.date.issued
2011-07  
dc.identifier.citation
Flores, Wilfredo C.; Mombello, Enrique Esteban; Jardini, José. A.; Rattá Gutiérrez, Giuseppe Aníbal; Corvo, Antonio M.; Expert system for the assessment of power transformer insulation condition based on type-2 fuzzy logic systems; Pergamon-Elsevier Science Ltd; Expert Systems with Applications; 38; 7; 7-2011; 8119-8127  
dc.identifier.issn
0957-4174  
dc.identifier.uri
http://hdl.handle.net/11336/189302  
dc.description.abstract
An efficient expert system for the power transformer condition assessment is presented in this paper. Through the application of Duval's triangle and the method of the gas ratios a first assessment of the transformer condition is obtained in the form of a dissolved gas analysis (DGA) diagnosis according IEC 60599. As a second step, a knowledge mining procedure is performed, by conducting surveys whose results are fed into a first Type-2 Fuzzy Logic System (T2-FLS), in order to initially evaluate the condition of the equipment taking only the results of dissolved gas analysis into account. The output of this first T2-FLS is used as the input of a second T2-FLS, which additionally weighs up the condition of the paper-oil system. The output of this last T2-FLS is given in terms of words easily understandable by the maintenance personnel. The proposed assessing methodology has been validated for several cases of transformers in service. © 2011 Elsevier Ltd. All rights reserved.  
dc.format
application/pdf  
dc.language.iso
eng  
dc.publisher
Pergamon-Elsevier Science Ltd  
dc.rights
info:eu-repo/semantics/openAccess  
dc.rights.uri
https://creativecommons.org/licenses/by-nc-sa/2.5/ar/  
dc.subject
DIAGNOSTIC REASONING  
dc.subject
KNOWLEDGE-BASED SYSTEMS  
dc.subject
POWER TRANSFORMER INSULATION  
dc.subject
POWER TRANSFORMERS  
dc.subject
TYPE-2 FUZZY LOGIC SYSTEMS  
dc.subject.classification
Ingeniería Eléctrica y Electrónica  
dc.subject.classification
Ingeniería Eléctrica, Ingeniería Electrónica e Ingeniería de la Información  
dc.subject.classification
INGENIERÍAS Y TECNOLOGÍAS  
dc.title
Expert system for the assessment of power transformer insulation condition based on type-2 fuzzy logic systems  
dc.type
info:eu-repo/semantics/article  
dc.type
info:ar-repo/semantics/artículo  
dc.type
info:eu-repo/semantics/publishedVersion  
dc.date.updated
2023-02-21T22:14:54Z  
dc.journal.volume
38  
dc.journal.number
7  
dc.journal.pagination
8119-8127  
dc.journal.pais
Estados Unidos  
dc.description.fil
Fil: Flores, Wilfredo C.. Universidad Nacional Autónoma de Honduras; Honduras. Universidad Nacional de San Juan; Argentina  
dc.description.fil
Fil: Mombello, Enrique Esteban. Universidad Nacional de San Juan; Argentina. Consejo Nacional de Investigaciones Científicas y Técnicas. Centro Científico Tecnológico Conicet - San Juan; Argentina  
dc.description.fil
Fil: Jardini, José. A.. Universidade de Sao Paulo; Brasil  
dc.description.fil
Fil: Rattá Gutiérrez, Giuseppe Aníbal. Universidad Nacional de San Juan; Argentina  
dc.description.fil
Fil: Corvo, Antonio M.. Companhia de Transmissão de Energía Elétrica Paulista; Brasil  
dc.journal.title
Expert Systems with Applications  
dc.relation.alternativeid
info:eu-repo/semantics/altIdentifier/url/https://www.sciencedirect.com/science/article/abs/pii/S0957417410015162  
dc.relation.alternativeid
info:eu-repo/semantics/altIdentifier/doi/http://dx.doi.org/10.1016/j.eswa.2010.12.153