Artículo
Expert system for the assessment of power transformer insulation condition based on type-2 fuzzy logic systems
Flores, Wilfredo C.; Mombello, Enrique Esteban
; Jardini, José. A.; Rattá Gutiérrez, Giuseppe Aníbal; Corvo, Antonio M.
Fecha de publicación:
07/2011
Editorial:
Pergamon-Elsevier Science Ltd
Revista:
Expert Systems with Applications
ISSN:
0957-4174
Idioma:
Inglés
Tipo de recurso:
Artículo publicado
Clasificación temática:
Resumen
An efficient expert system for the power transformer condition assessment is presented in this paper. Through the application of Duval's triangle and the method of the gas ratios a first assessment of the transformer condition is obtained in the form of a dissolved gas analysis (DGA) diagnosis according IEC 60599. As a second step, a knowledge mining procedure is performed, by conducting surveys whose results are fed into a first Type-2 Fuzzy Logic System (T2-FLS), in order to initially evaluate the condition of the equipment taking only the results of dissolved gas analysis into account. The output of this first T2-FLS is used as the input of a second T2-FLS, which additionally weighs up the condition of the paper-oil system. The output of this last T2-FLS is given in terms of words easily understandable by the maintenance personnel. The proposed assessing methodology has been validated for several cases of transformers in service. © 2011 Elsevier Ltd. All rights reserved.
Archivos asociados
Licencia
Identificadores
Colecciones
Articulos(CCT - SAN JUAN)
Articulos de CENTRO CIENTIFICO TECNOLOGICO CONICET - SAN JUAN
Articulos de CENTRO CIENTIFICO TECNOLOGICO CONICET - SAN JUAN
Citación
Flores, Wilfredo C.; Mombello, Enrique Esteban; Jardini, José. A.; Rattá Gutiérrez, Giuseppe Aníbal; Corvo, Antonio M.; Expert system for the assessment of power transformer insulation condition based on type-2 fuzzy logic systems; Pergamon-Elsevier Science Ltd; Expert Systems with Applications; 38; 7; 7-2011; 8119-8127
Compartir
Altmétricas