dc.identifier.citation
Otegui, Luis Jose; Fazzini, Pablo Gabriel; Root causes of fire in a solvent pipe at a petrochemical plant; Pergamon-Elsevier Science Ltd; Engineering Failure Analysis; 16; 6; 2-9-2009; 1903-1911  
dc.identifier.issn
1350-6307  
dc.identifier.uri
http://hdl.handle.net/11336/66060  
dc.description.abstract
The root causes of a leak followed by a small fire in a 2 in. solvent pipe in a Petrochemical Plant are discussed. The fire occurred during blanket heating to 300 °C to dissolve polymer clogs. Fractographic and metallographic analyses showed that the failure is characterized by intergranular through the thickness propagation of longitudinal cracks initiated at the outer pipe surface. This cracking mode is called r-type cavitation. The leaking solvent self ignited, polymer deposits inside the pipe carbonized, microstructure changed. All these indicate that pipe temperature during blanket heating reached 550 °C, much above the specified 300 °C maximum. At this temperature yield strength of the pipe material got below nominal hoop stress due to normal internal pressure. The failure of the temperature control system in one of the heating blanket sets was the main event that caused the fire. However, other conditions and exceeded barriers are discussed, related with safety procedures and insufficient support of the ongoing investigation by the contractor involved in the incident. As a result, changes in the declogging and safety procedures were introduced. © 2008 Elsevier Ltd. All rights reserved.  
dc.format
application/pdf  
dc.language.iso
eng  
dc.publisher
Pergamon-Elsevier Science Ltd  
dc.rights
info:eu-repo/semantics/openAccess  
dc.rights.uri
https://creativecommons.org/licenses/by-nc-sa/2.5/ar/  
dc.subject
High Temperature  
dc.subject
Maintenance  
dc.subject
Petrochemical Plant  
dc.subject
Pipe Failure  
dc.subject.classification
Física de los Materiales Condensados  
dc.subject.classification
Ciencias Físicas  
dc.subject.classification
CIENCIAS NATURALES Y EXACTAS  
dc.subject.classification
Recubrimientos y Películas  
dc.subject.classification
Ingeniería de los Materiales  
dc.subject.classification
INGENIERÍAS Y TECNOLOGÍAS  
dc.title
Root causes of fire in a solvent pipe at a petrochemical plant  
dc.type
info:eu-repo/semantics/article  
dc.type
info:ar-repo/semantics/artículo  
dc.type
info:eu-repo/semantics/publishedVersion  
dc.date.updated
2018-12-05T14:36:17Z  
dc.journal.volume
16  
dc.journal.number
6  
dc.journal.pagination
1903-1911  
dc.journal.pais
Reino Unido  
dc.journal.ciudad
Londres  
dc.description.fil
Fil: Otegui, Luis Jose. Consejo Nacional de Investigaciones Científicas y Técnicas. Centro Científico Tecnológico Conicet - Mar del Plata. Instituto de Investigaciones en Ciencia y Tecnología de Materiales. Universidad Nacional de Mar del Plata. Facultad de Ingeniería. Instituto de Investigaciones en Ciencia y Tecnología de Materiales; Argentina  
dc.description.fil
Fil: Fazzini, Pablo Gabriel. GIE S.A.; Argentina  
dc.journal.title
Engineering Failure Analysis  
dc.relation.alternativeid
info:eu-repo/semantics/altIdentifier/url/https://www.sciencedirect.com/science/article/pii/S1350630708002264  
dc.relation.alternativeid
info:eu-repo/semantics/altIdentifier/doi/https://dx.doi.org/10.1016/j.engfailanal.2008.09.029