Artículo
Power Transformer Condition Assessment Using DGA and FRA
Fecha de publicación:
11/2016
Editorial:
Institute of Electrical and Electronics Engineers
Revista:
IEEE Latin America Transactions
e-ISSN:
1548-0992
Idioma:
Español
Tipo de recurso:
Artículo publicado
Clasificación temática:
Resumen
Power transformer condition assessment is a very complex task but also of high priority for power system reliability. Several diagnosis techniques have been published, specifically; insulation system condition assessment (paper and oil) using Dissolve Gas Analysis (DGA), and to assess winding and core condition, using Frequency Response Analysis (FRA). Results of these different techniques represent complementary or corroborative information of the final transformer condition. Therefore, unification of both techniques information helps to assess accurately transformer condition, which is very important in transformers management field and its failure risk estimation. In this paper, a novel method for DGA and FRA results unification is proposed, which is based on fuzzy sets application in failures detection and interpretation stages.
Archivos asociados
Licencia
Identificadores
Colecciones
Articulos(IEE)
Articulos de INSTITUTO DE ENERGIA ELECTRICA
Articulos de INSTITUTO DE ENERGIA ELECTRICA
Citación
Gonzales Arispe, Jimmy Cesar; Mombello, Enrique Esteban; Power Transformer Condition Assessment Using DGA and FRA; Institute of Electrical and Electronics Engineers; IEEE Latin America Transactions; 14; 11; 11-2016; 4527-4533
Compartir