dc.description.abstract
The causes of recent fires in hydrocarbon heaters are discussed in this paper. In particular, failures are chosen for which root causes involve trying to get around existing operational shortcomings by making changes to control, instead of carrying out a proper Root Cause Analysis to identify actual causes of deficiencies. In one case, the heater would extinguish due to the poor characteristics of fuel gas. A restart routine was devised, in which previous purging was avoided. In the other case, turning off one burner would turn off the remaining. Instead of addressing the reason why a burner would turn off, the operator modified gas inlet control so that the remaining burners would remain on. Details are given of the chain of events that led to these failures. It is concluded that heaters should be carefully chosen or designed to meet specific operation requirements. Modifications should be avoided whenever possible and carefully planned, in association with the manufacturer when they are unavoidable. In every case, safety systems should be in accordance with modern safety standards.  
dc.format
application/pdf  
dc.language.iso
eng  
dc.publisher
Pergamon-Elsevier Science Ltd  
dc.rights
info:eu-repo/semantics/openAccess  
dc.rights.uri
https://creativecommons.org/licenses/by-nc-nd/2.5/ar/  
dc.subject
Design Flaws  
dc.subject
Failures  
dc.subject
Fires  
dc.subject
Oil Heaters  
dc.subject
Safety And Control Systems  
dc.subject.classification
Otras Ingenierías y Tecnologías  
dc.subject.classification
Otras Ingenierías y Tecnologías  
dc.subject.classification
INGENIERÍAS Y TECNOLOGÍAS  
dc.title
Failures in cabin type hydrocarbon heaters due to inadequate fuel control  
dc.type
info:eu-repo/semantics/article  
dc.type
info:ar-repo/semantics/artículo  
dc.type
info:eu-repo/semantics/publishedVersion  
dc.date.updated
2018-07-11T17:25:15Z  
dc.journal.volume
21  
dc.journal.pagination
31-39  
dc.journal.pais
Estados Unidos  
dc.description.fil
Fil: Booman, Janine. GIE; Argentina. Universidad Nacional de Rosario; Argentina  
dc.description.fil
Fil: González, M.O.. Integrity of Oil & Gas Facilities; Argentina  
dc.description.fil
Fil: Otegui, Luis Jose. Consejo Nacional de Investigaciones Científicas y Técnicas. Centro Científico Tecnológico Conicet - Mar del Plata. Instituto de Investigaciones en Ciencia y Tecnología de Materiales. Universidad Nacional de Mar del Plata. Facultad de Ingeniería. Instituto de Investigaciones en Ciencia y Tecnología de Materiales; Argentina  
dc.journal.title
Engineering Failure Analysis  
dc.relation.alternativeid
info:eu-repo/semantics/altIdentifier/doi/http://dx.doi.org/10.1016/j.engfailanal.2011.11.012  
dc.relation.alternativeid
info:eu-repo/semantics/altIdentifier/url/https://www.sciencedirect.com/science/article/pii/S1350630711002792