Mostrar el registro sencillo del ítem
dc.contributor.author
Tovar, R.
dc.contributor.author
Linden, P. F.
dc.contributor.author
Thomas, Luis Pablo
dc.date.available
2024-07-12T14:08:16Z
dc.date.issued
2007-12
dc.identifier.citation
Tovar, R.; Linden, P. F.; Thomas, Luis Pablo; Hybrid ventilation in two interconnected rooms with a buoyancy source; Pergamon-Elsevier Science Ltd; Solar Energy; 81; 5; 12-2007; 683-691
dc.identifier.issn
0038-092X
dc.identifier.uri
http://hdl.handle.net/11336/239831
dc.description.abstract
The design of energy efficient buildings and the potential for using solar energy for heating and cooling is contingent upon optimizing the building ventilation systems. In this paper we study the ventilation of two interconnected spaces, such as adjacent offices or areas in an open plan office. The goal is to locate return vents to increase the efficiency of night ventilation and to reduce energy consumption.The flow in two interconnected rooms of similar sizes is studied experimentally using a tank divided by an interior vertical wall. A forced buoyancy source with a finite volume flux is located in the ceiling of one-room and an unforced vent is opened in the ceiling of the other room.The goal of the study is to understand the transient cooling/heating that occurs in this two-room system when a forced cold-air vent is located in the ceiling of the first room and a return ventilation exit is located in the second. In particular, we investigate the effects of varying the number of openings and their vertical positions in the interconnecting wall. First, a single opening at the bottom, middle or top of the shared wall is examined. Second, the case of two openings in the wall is considered, with the openings located at the top–bottom,top –middle, bottom –middle, and finally at two mid locations in the wall. The results are compared with the one-room case, which represents the reference case. It was found that, irrespective of the number and locations of the openings, the flow evolves into a quasi-stationary stably stratified two-layer system, with the depths of the layers being different in each room.The average temperature inside each room initially decreases linearly with time and approaches the supply-air temperature at large times.This initial linear decrease holds until cold-air leaves the unforced room through the top-vent at time t_e. Subsequently, temperature decreases as an exponential function of time with a characteristic filling time s =V /Q_s ,where V is the total volume of both rooms and Q_s is the source volume flux. The efficiency of the ventilation depends on the time t_e, and this depends, in turn, on an exchange flow that is established between the two-rooms by the differences in density in each room. For a single opening, the exchange flow takes place as a two-way flow in the opening, while for two openings the flow is from the forced room through the lower opening and in the opposite direction through the upper opening. When the upper opening is located below the ceiling, this flow from the unforced room ‘shields ’the return vent from the dense fluid, thereby increasing the efficiency of the ventilation.
dc.format
application/pdf
dc.language.iso
eng
dc.publisher
Pergamon-Elsevier Science Ltd
dc.rights
info:eu-repo/semantics/openAccess
dc.rights.uri
https://creativecommons.org/licenses/by-nc-sa/2.5/ar/
dc.subject
Natural Ventilation
dc.subject
Buoyancy-Driven Flows
dc.subject
Thermal sources
dc.subject.classification
Otras Ciencias Físicas
dc.subject.classification
Ciencias Físicas
dc.subject.classification
CIENCIAS NATURALES Y EXACTAS
dc.title
Hybrid ventilation in two interconnected rooms with a buoyancy source
dc.type
info:eu-repo/semantics/article
dc.type
info:ar-repo/semantics/artículo
dc.type
info:eu-repo/semantics/publishedVersion
dc.date.updated
2024-07-11T11:43:49Z
dc.journal.volume
81
dc.journal.number
5
dc.journal.pagination
683-691
dc.journal.pais
Estados Unidos
dc.description.fil
Fil: Tovar, R.. Universidad Nacional Autónoma de México; México
dc.description.fil
Fil: Linden, P. F.. University of California at San Diego; Estados Unidos
dc.description.fil
Fil: Thomas, Luis Pablo. Universidad Nacional del Centro de la Provincia de Buenos Aires. Facultad de Ciencias Exactas. Instituto de Física Arroyo Seco; Argentina. Consejo Nacional de Investigaciones Científicas y Técnicas. Centro Científico Tecnológico Conicet - Tandil; Argentina
dc.journal.title
Solar Energy
dc.relation.alternativeid
info:eu-repo/semantics/altIdentifier/url/https://www.sciencedirect.com/science/article/pii/S0038092X0600226X
dc.relation.alternativeid
info:eu-repo/semantics/altIdentifier/doi/http://dx.doi.org/10.1016/j.solener.2006.08.009